Determining the Maximum Output of Underfloor Heating and Bathroom Radiator

Written by Divine Bunda-Rühl

The maximum heating output of underfloor heating systems is directly related to the maximum permissible surface temperature:

  • In living areas, the maximum surface temperature is 29 °C.

  • In bathrooms, it can be up to 33 °C.

Calculation Basis

The calculation of the maximum heating output is based on the following formula:

HL = 8.92 × (surface temperature – room temperature)^1.1

Bathroom radiators are generally not intended to cover the full heating load of a room. Instead, they serve primarily aesthetic and functional purposes — for example, for drying towels.

For this reason, we do not evaluate bathroom radiators based on supply and return temperatures, but solely based on their maximum achievable output.
​

Calculation Basis

As a reference, we use the standard output as defined in the technical literature by Recknagel, based on a temperature level of 75/65/20 °C.
​

In addition, we apply a general performance reduction of 50% to realistically account for the impact of towels hanging on the radiator.